UPS Online Double Conversion Transformer Based Double IGBT HT5000IG(80~500KVA)

Ups series HT5000IG online double conversion technology for true isolation between input and output. Availability is achieved through zero transfer time for critical loads.UPS is highly reliable and flexible. features a digitally controlled IGBT input rectifier and output inverter an intelligent low harmonic pulse-width modulation (PWM) output, state-of-the-art electronic battery isolation circuitry, and an easy-to-navigate local touch screen interface .

Category:

Description

Ups series HT5000IG online Double Conversion technology for true isolation between input and output. Availability is achieved through zero transfer time for critical loads.UPS is highly reliable and flexible. features a digitally controlled IGBT input rectifier and output inverter an intelligent low harmonic pulse-width modulation (PWM) output, state-of-the-art electronic battery isolation circuitry, and an easy-to-navigate local touch screen interface.

There are two main benefits of a transformer-based ups series HT5000IG Firstly it is generally accepted that they are more robust there are less points of failure. Secondly, the transformer provides galvanic isolation, a separation of the input and output supplies, which protects the load from any spikes, surges, or electrical noise.

Online double conversion mode with an output power factor of 0.9 providing 12% more active power compare to UPS with a power factor of 0.8

High input power factor and use of an IGBT Rectifier eliminate the use of oversized input feeders

Input power factor > 0.99, input THDi ≤ 3%, output THDV ≤ 5%

Large display panel provides metering, statistics, alarm history, and an active mimic screen

With emergency shutdown (EPO) button interface

Dynamic battery management screen optimizes battery function to lengthen service life and allow cold restart of the UPS

Output isolation transformer using winding makes strong capability with unbalanced loads produced to comply with Standards for supplying critical loads

N+X redundancy parallel up to 6 units (optional)

Generator compatible

 <!doctype html public “-//w3c//dtd xhtml 1.0 transitional//en” “http://www.w3.org/tr/xhtml1/dtd/xhtml1-transitional.dtd”>

<![if supportMisalignedColumns]><![endif]>

 

Swipe left on mobile

MODEL HT 5800 IG HT 51000 IG HT 51200 IG HT 51600 IG HT 52000 IG HT 53000 IG HT 55000 IG
POWER KVA 80 KVA 100 KVA 120 KVA 160 KVA 200 KVA 300 KVA 500 KVA
KW 72KW 90 KW 108 KW 144 KW 180 KW 270 KW 450 KW
INPUT Rated voltage 380V / 400V / 415V _ Three-phase + N       
Voltage range   346 V ~ 456 V ( full load) 304 V ~ 346 V (power derating 10%)  
Frequency range 50 / 60 Hz ± 5Hz
Power factor ≥ 0.99 @ Full load
Current distortion THDI ≤  3% @ 100% Linear load
Rectifier delay start 10s ( 1 ~ 300 settable )
Bypass voltage range ±  20 %  (settable )
OUTPUT Rated voltage 380 V / 400 V / 415 V _ Three-phase + N
Voltage regulation ± 1 %
Frequency  50 / 60 Hz  ± 0.1 % in battery mode
power factor 0 . 9
Crest factor 3:01
Total harmonic distortion THDV  ≤ 2 % (linear load) ; ≤ 5 % (non-linear load)
Transfer time 0 ms
Inverter overload capability 105 % ~ 110 % for 60 minutes;
110 % ~ 125 % for 10 minutes;
BATTERIES DC Voltage 600 Vdc (support 576 Vdc / 588 Vdc / 612 Vde / 624 Vdc ) @ 50 pcs 12V ( support 48 / 49 / 51/52 pcs)
Charging current Charging rate x battery capacity x number of battery
SYSTEM Smart active efficiency Line mode ≥ 93 % , ECO mode ≥ 98 % , battery mode ≥ 93 %
Parallel numbers MAX . 6
Protections Short-circuit, overload, overtemperature, overvoltage, Undervoltage , battery low voltage, and fan failure
communications Standard configuration: RS232, RS485, dry contacts
Optional configuration  SNMP card, temperature compensation, SMS alarms
Display 5.7 inches LCD touch screen
OTHERS Operating temperature Storage  0 ~ 40°C / — 25°C ~ + 55°C  ( without battery )
Relative humidity 0% ~ 95%  ( non – condensing )
Altitude  ≤ 1000 m. Above 1000 m, derating 1% for each additional 100 m
IP rating IP 20
Noise level at 1m <  65 dB < 70 dB
PHYSICAL Dimensions                              (W x D x H) (m m) 800 x 800 x 1800 800 x 860                      x 1700 1210 x 860 x 1950 2380 x 860                 x 1950
Packaged dimensions            (W x D x H) (m m) 900 x 900 x 2050 900 x 1000                     x 1950 1300 x 1000 x 2200 1300 x 1000               x 2200 (x2)
Net / Gross weight (kg) 580 / 630 630 / 680 680 / 730 680 / 730 1135 / 1200 1355 / 1420 2300 / 2410

 

 