UPS TRITON M3, online double conversion, 120-200 kVA

With the TRITON EFFEKTA® offers a modern, modular design, online double-conversion UPS with 3-phase input & output. For simple commissioning, operation and maintenan- ce of all controls, ports and the module are accessible from the front.

Category:

Description

With the TRITON EFFEKTA® offers a modern, modular design, online double-conversion UPS with 3-phase input & output. For simple commissioning, operation and maintenan- ce of all controls, ports and the module are accessible from the front.

SNMP/web or relay card for monitoring in network environments

Additional battery modules to provide an uninterruptible power supply for up to several hours

External manual bypass for planned UPS maintenance work or replacement of the UPS unit without shutting it down

Extended warranty arrangements

Customer-oriented individual service and maintenance contracts

UPS classification VFI-SS-111 (IEC 62040-3)

Online double conversion with sinusoidal output

Easy maintenance through modular design

High efficiency (up to 95%)

Switchable to ECO mode (> 98%, line-interactive)

High output power factor (0,9)

Temperature-controlled fan

100% suitable for load imbalances

Programmable maintenance management

Extensive communication interfaces

24 months warranty

Swipe left on mobile







TRITON M3 120 kVA  160 kVA  200 kVA 
Power Power in VA  120 160 200
Power in W  108 144 180
Autonomy time
100% / 50% load
(cos. phi 0,7)
With internal batteries in minutes i7/i17 i9/i19 i6/i13
Longer autonomy times on request
Technology  Online double conversion  VFI-SS-111 in accordance with IEC 62040-3
Phase  Input / Output  3-phase / 3-phase
Input Nominal voltage  380/400/415 VAC
Input voltage range  208-478 VAC
Input frequency range  50/60 Hz (Auto-Sensing)
Circuit feedback THDI  < 2%
Output  Output voltage  380/400/415 VAC
Voltage Regulation  ±1%
Power factor  0,9
Frequency Range  50 Hz or 60 Hz ± 1 Hz
Transfer time  none
Overload Capability (Line Mode)  < 125%: 10 min. / < 150%: 1 min.
Voltage form  sine wave
Efficiency  Normal mode / ECO mode  max. 95 % / 98 %
Battery Type  Maintenance free lead-acid battery
Life time  10 years
Charging current (max)  30 A  40 A  50 A
Recharging time  5 h, dependent on accumulator capacity
Communication Interface  USB, RS232, RS485, EPO, REPO dry contact, Temp. sensor contact
Communication cards  Optional relay contacts or SNMP card
Slot for communication cards  2
Display  multi language LC-Display
Parallel switching  Max. 4 systems for redundancy or to boost performance
Dimensions /
Weigh
Dimensions UPS (H x W x D in mm)  1600 x 600 x 850
Weight UPS (without accumulators)   345 kg  379 kg 413 kg
Dimensions battery cabinet with standard configuration    (H x W x D in mm) 2000 x 600 x 1100
Weight battery cabinet with standard configuration    1421 kg 2 x 1076 kg 2152 kg
Protection  IP 20 (optionally higher protection class possible)
Terminals Input  Fixed connection on terminals
Output Fixed connection on terminals
Environmental
conditions
Temperature  0°C – 40°C, 20°C recommended
Humidity  0-90 % RH @ 0- 40°C (non condensing)
Acoustic Noise  < 70 dB
Safety / Enclosure  Safety  EN 62040-1
EMC  EN 62040-2, class C3
Certifications  CE