UPS TRITON M3, online double conversion, 120-200 kVA
With the TRITON EFFEKTA® offers a modern, modular design, online double-conversion UPS with 3-phase input & output. For simple commissioning, operation and maintenan- ce of all controls, ports and the module are accessible from the front.
Description
With the TRITON EFFEKTA® offers a modern, modular design, online double-conversion UPS with 3-phase input & output. For simple commissioning, operation and maintenan- ce of all controls, ports and the module are accessible from the front.
SNMP/web or relay card for monitoring in network environments
Additional battery modules to provide an uninterruptible power supply for up to several hours
External manual bypass for planned UPS maintenance work or replacement of the UPS unit without shutting it down
Extended warranty arrangements
Customer-oriented individual service and maintenance contracts
UPS classification VFI-SS-111 (IEC 62040-3)
Online double conversion with sinusoidal output
Easy maintenance through modular design
High efficiency (up to 95%)
Switchable to ECO mode (> 98%, line-interactive)
High output power factor (0,9)
Temperature-controlled fan
100% suitable for load imbalances
Programmable maintenance management
Extensive communication interfaces
24 months warranty
Swipe left on mobile
TRITON M3 | 120 kVA | 160 kVA | 200 kVA | |
Power | Power in VA | 120 | 160 | 200 |
Power in W | 108 | 144 | 180 | |
Autonomy time 100% / 50% load (cos. phi 0,7) |
With internal batteries in minutes | i7/i17 | i9/i19 | i6/i13 |
Longer autonomy times on request | ||||
Technology | Online double conversion | VFI-SS-111 in accordance with IEC 62040-3 | ||
Phase | Input / Output | 3-phase / 3-phase | ||
Input | Nominal voltage | 380/400/415 VAC | ||
Input voltage range | 208-478 VAC | |||
Input frequency range | 50/60 Hz (Auto-Sensing) | |||
Circuit feedback THDI | < 2% | |||
Output | Output voltage | 380/400/415 VAC | ||
Voltage Regulation | ±1% | |||
Power factor | 0,9 | |||
Frequency Range | 50 Hz or 60 Hz ± 1 Hz | |||
Transfer time | none | |||
Overload Capability (Line Mode) | < 125%: 10 min. / < 150%: 1 min. | |||
Voltage form | sine wave | |||
Efficiency | Normal mode / ECO mode | max. 95 % / 98 % | ||
Battery | Type | Maintenance free lead-acid battery | ||
Life time | 10 years | |||
Charging current (max) | 30 A | 40 A | 50 A | |
Recharging time | 5 h, dependent on accumulator capacity | |||
Communication | Interface | USB, RS232, RS485, EPO, REPO dry contact, Temp. sensor contact | ||
Communication cards | Optional relay contacts or SNMP card | |||
Slot for communication cards | 2 | |||
Display | multi language LC-Display | |||
Parallel switching | Max. 4 systems for redundancy or to boost performance | |||
Dimensions / Weigh |
Dimensions UPS (H x W x D in mm) | 1600 x 600 x 850 | ||
Weight UPS (without accumulators) | 345 kg | 379 kg | 413 kg | |
Dimensions battery cabinet with standard configuration (H x W x D in mm) | 2000 x 600 x 1100 | |||
1421 kg | 2 x 1076 kg | 2152 kg | ||
Protection | IP 20 (optionally higher protection class possible) | |||
Terminals | Input | Fixed connection on terminals | ||
Output Fixed connection on terminals | ||||
Environmental conditions |
Temperature | 0°C – 40°C, 20°C recommended | ||
Humidity | 0-90 % RH @ 0- 40°C (non condensing) | |||
Acoustic Noise | < 70 dB | |||
Safety / Enclosure | Safety | EN 62040-1 | ||
EMC | EN 62040-2, class C3 | |||
Certifications | CE |