UPS Online Double Conversion Transformer Based HT3000T(6~10KVA)
LCD display to show input and output voltage, load, frequency, inside temperature of the device,battery charge load
Protection: short circuits, high and low voltages, overload, reverse connection of batteries and High charge, etc.
Connecting to parallel card & isolated transformer in the bypass section
Communication with PC by RS232 (standard), USB / RS485 / SNMP / Dry Call (optional)
Description
Online Double Conversion, transformer base technology with stable and uninterrupted power and complete sine waveform linear and non-linear loads at maximum load consumption
Output Power factor of 0.8 & Input power factor 0.99 and Active Power Factor Correction (Apfc)
Select current charging : 2A / 4A / 6A / 8A / 10A / 12A
Overload capacity up to 105% ~ 125% for 10 min , 125% ~ 150% for 1 min ,150%~200% for 200 ms ,Up to200%for 100 ms
wide input frequency range for operation with variety of generators in the range of 40 to 70 Hz and proper stabilization of the output frequency of 50 Hz with a telorance of 0.1
LCD display to show input and output voltage, load, frequency, inside temperature of the device,battery charge load
Protection: short circuits, high and low voltages, overload, reverse connection of batteries and High charge, etc.
Connecting to parallel card
Communication with PC by RS232 (standard), USB / RS485 / SNMP / Dry Call (optional)
Adjusting the output voltage ,EOD, automatic start, bypass mode and adjusting the frequency and ECO MODE through the LCD display panel
Adjusting the output frequency at 50 and 60 Hz and having Auto frequency Sensing
Cold Start and automatic start-up after connecting the city electricity and having settable delay
DSP (digital signal processors )control technology Effective software and hardware protection
Shut down automatically in emergency time (EPO)
<!doctype html public “-//w3c//dtd xhtml 1.0 transitional//en” “http://www.w3.org/tr/xhtml1/dtd/xhtml1-transitional.dtd”>
<![if supportMisalignedColumns]><![endif]>
Swipe left on mobile
MODEL | HT 3060T | HT 3100T | |
POWER | VA | 6000 | 10000 |
W | 4800 | 8000 | |
INPUT | Rated voltage | 220 / 230 / 240 V | |
Voltage range | 165 ~ 275 V | ||
Rated frequency | 50 Hz/ 60 Hz | ||
Frequency range | 40 ~ 70 Hz | ||
Bypass voltage range | ± 25 V | ||
OUTPUT | Rated voltage | 220 / 230 / 240 V (settable) | |
Voltage precision | ±1% | ||
Frequency | 50/60 ± 0.1 Hz in battery mode | ||
Rated frequency | 50 Hz/ 60 Hz (settable) | ||
Power factor | i0.8 | ||
Crest factor | 3˸1 | ||
THDV | ≤ 2% (linear load)≤ 5% (non-linear load) | ||
Waveform | Sinusoidal | ||
Overload | 105% ~ 125% for 10 min , 125% ~ 150% for 1 min ,150%~100% for 200 ms , 200%for 100 ms | ||
BATTERIES | Dc voltage | 192 VDC | |
Charging current | Default 8A (2A ~ 12A selectable) | ||
Number of battery | 12V x 16 pcs | ||
Charging voltage | 216 VDC | ||
EOD | 168 VDC | ||
SYSTEM | Protections | Short circuit , Overload, Overvoltage , Undervoltage ,Low battery , Over temperature | |
Communications | RS232 / USB (standard) RS485 / SNMP / dry contacts (optional) | ||
OTHERS | Operaring temperature | 0°C~ 40°C | |
Relative humidity | 0~95% (non-condensing) | ||
Altitude | ≤1000m (derating 1% for each additional 100 m) | ||
IP rating | IP 20 | ||
Noise level (1m) | < 60 dB | ||
Transfer time | 0 ms | ||
PHYSICAL | Dimensions (W x D x H) (mm) | 215 x 580 x 600 | 315 x 600 x 900 |
Packaged dimensions (WxDxH) (mm) |
330 x 720 x 800 | 435 x 700 x 1100 | |
Net weight (kg) | 55 | 105 | |
Gross werghi (kg) | 65 | 115 |