UPS Double Conversion HT3000(1~10KVA)

Online Double Conversion technology with stable and uninterrupted power and complete sine waveform in linear and non-linear load at maximum load consumption

Input power factor 0.99 and Active Power Factor Correction (APFC)

Output Power factor of 0.9

DSP (digital signal processors )control technology

Category:

Description

Online Double Conversion technology with stable and uninterrupted power and complete sine waveform in linear and non-linear load at maximum load consumption

Input power factor 0.99 and Active Power Factor Correction (APFC)

Output Power factor of 0.9

DSP (digital signal processors )control technology

Input voltage range from 110 volts to 300 volt

Wide input frequency range for operation with variety of generators in the range of 40 to 70 Hz and proper stabilization of the output frequency of 50 Hz with a tolerance of 0.1

LCD display to show input and output voltage, power as VA & frequency, inside temperature of the device, battery charge and load consumption rate

Adjust the output Voltage,Selectable battery shutdown voltage (EOD) , automatic start, bypass mode and and ECO mode through the LCD display panel

Advanced Battery Management (ABM) to control battery charge , discharge and fast and stable charge in about three hours and prevention of excessive battery discharge

With EMI protection filters and RFI varistor and protection against over current and over voltage, short-circuit, DC reverse voltage and lightning

Start without the need for city electricity (Cold Start) and automatic start-up after connecting the city electricity and settable delayed start when power is restored

Flexible battery configuration in UPS 6K & 10K (168/180/192/204/216/228/240 settable)

Adjust the output frequency at 50 and 60 Hz and has Auto Sensing Frequency

Effective software and hardware protection

Function at relative Humidity between 0 to 95% and temperature between 0 to 40 degrees Celsius

Turn off the device automatically in on sump hot no-load mode (ECO Mode)

Shut down automatically in emergency time

Communication with PC by RS232 (standard), USB / RS485 / SNMP / Dry Call (optional)

<!octype html public “-//w3c//dtd xhtml 1.0 transitional//en” “http://www.w3.org/tr/xhtml1/dtd/xhtml1-transitional.dtd”>

<![if supportMisalignedColumns]><![endif]>

 

Swipe left on mobile

MODEL HT 3010 HT 3020 HT 3030 HT 3060 HT 3100
POWER VA 1000 2000 3000 6000 10000
W 900 1800 2700 5400 9000
INPUT Rated voltage 208 V/ 220 V/ 230 V/240 V
Voltage range 110 ~ 176 V (Linear derating between 50% and 100% load)  176 ~ 280 V (no derating)  280 ~ 300 V (derating 50%) 
Rated frequency 50 / 60 Hz (auto-sense)
Frequency 40 ~ 70 Hz  (auto-sense)
Power factor ≥ 0.99
Total harmonic distortion THDI ≤ 6% THDI ≤ 5%
Bypass voltage range  – 25% ~ +15% (settable) 1– 40 %~ +15% (settable)
OUTPUT Voltage 208 V/ 220 V/ 230 V/ 240 V (settable via LCD)
Power factor 0.9
Voltage regulation ± 1%
Frequency Synchronized with utility in mains mode 50/60Hz ± 0.1 Hz in battery mode
Waveform Sinusoidal
Crest factor i3:1
Harmonic distortion ≤ 2% (linear load)  ≤ 5% (non-linear load)
Transfer time Mains mode to battery mode  0 ms – Inverter mode to bypass mode : 0 ms
Overload 1~3 105% ~ 125% for 1 min,125% ~ 150% for 30 s, >150% for 300 ms
6~10 102% ~125% :  in 10 mins,125% ~150% : in 1 min ,> 150% : in 0/5 s
BATTERIES DC voltage 36 72 72 ~ 96 192~240
Charging             current internal  model 1A
external model  6A 8A
Recharge              time internal  model 90% capacity restored in 3 hours 90% capacity restored in 4 hours
external model  depend on the capacity of  battery
SYSTEM   EffIciency Mains mode ≥ 90 % ≥ 91% ≥ 92% ≥ 93 %
Battery mode ≥ 85 % ≥ 86% ≥ 87% ≥ 91 %
ECO mode ≥ 95% ≥ 96% ≥ 97% ≥ 98 %
Display LCD + LED
Communications RS232 (standard) USB & SNMP (optional)
Alarms Overload, Battery mode, battery voltage low, fans fault etc
OTEHRS Humidity Operating temperature 0 ~ 90% (non – condensing), 0°C ~ 40°C
IP rating IP 20
Noise level ≤ 50 dB (1m) ≤ 55 dB (1m)
PHYSICAL Dimensions   (WxDxH) (mm) internal N 144 x 414 x 214 191 x 418 x 335 191 x 464 x 332 191 x 465 x 710
external X 144 x 336 x 214 191 x 418 x 335 191 x 465 x 350
Packaged dimensions         (WxDxH) (mm) internal N 230 x 492 x 320 280 x 533 x 437 210 x 573 x 472 310 x 645 x 895
external X 232 x 417 x 318 318 x 533 x 471 265 x 575 x 435
Net weight (kg) 13 (N) 6 (X) 25.7 27  (N) 11 (X) 58 (N) 15.5 (X) 67 (N) 16.5 (X)
Gross weight (kg) 14.5 (N) 7 (X) 27.4 29  (N) 12.5 (X) 65 (N) 18 (X) 73 (N) 18 (X)

 

 