150 kVA 460V 60Hz to 415V/400V 50Hz Converter

150 kVA 3 phase 460V 60 Hz to 415V, 400V 50 Hz static frequency converter, adjustable output Hertz (40.0 Hz – 400 Hz) and Volt (0 – 520V), built-in step-down/step-up transformers.

Category:

Description

150 kVA 3 phase 460V 60 Hz to 415V, 400V 50 Hz static frequency converter, adjustable output Hertz (40.0 Hz – 400 Hz) and Volt (0 – 520V), built-in step-down/step-up transformers.

GoHz 150 kVA static frequency converter for converting three phase 460V 60Hz to 415V 50Hz, 400V 50Hz, 420V 50Hz etc. Output voltage is adjustable from 0 – 520V three phase.

Tips: Can a 60Hz motor run on 50Hz Power?
When using a 60Hz motor in 50Hz duty
1) It will turn 20% slower.
2) Cooling will drop dramatically.
3) The load’s horsepower requirements will drop, possibly dramatically.
4) V/f will increase possibly causing a large increase in current draw.

The cooling will reduce dramatically. Is it enough to matter? This depends on how the load has decreased. If the horsepower requirement dropped because the load has decreased the current will drop and less heat will be released internally. You would want to take temperature measurements until the motor reaches a steady state temperature running in its new frequency application.

The most serious issue is the V/Hz issue. The V/Hz will increase. Likely enough to cause a large increase in the motor’s current. This coupled with the reduced cooling may cause rapid overheating. However the V/Hz problem can be fully mitigated!

Another way to think of this is:
New voltage = Old voltage x 50/60
New speed = Old speed x 50/60
New Horsepower = Old horsepower x 50/60
Note: This would instead be 60/50 for a 50 to 60 Hz conversion.
So it is up to you to decide how to handle your equipment.

Model HZ-50-33150
Capacity 150 kVA
Dimension 1500*860*1430 mm
Weight 800kg
Input Voltage 3 Phase 4 Wire: Wye Type 190/110, 200/115, 208/120, 220/128, 230/132, 240/139V ±10% (option *)
3 Phase 4 Wire: Wye Type 380/220, 400/230, 415/240, 440/254, 460/265, 480/277V ± 10% (option *)
3 Phase 4 Wire: Della Type 220, 230, 240, 380, 400, 415, 440V ± 10% (option *)
Frequency 50 Hz, 60 Hz or 400 Hz ± 5%
Output Voltage, current 110V Setting (Low grade): 0-150V (phase voltage), 0-260V (line voltage) 418A
220V Setting (High grade): 0-300V (phase voltage), 0-520V (line voltage) 209A
Load stabilization Rate ≤±1%
Frequency 50 Hz, 60 Hz up to 400 Hz adjustable
Note:
-When the output is 400Hz, the load capacity can only reach 50% of the rated capacity.
-When the output is ≤120Hz, the load capacity can reach 100% of the rated value.
-You can just adjust converter output frequency in the range (40-400Hz) for 400Hz option.
Frequency Stability ≤±0.01%
Harmonic Distortion Pure Sine Wave ≤2%
Frequency meter 4 digit, digital frequency meter, resolution 0.1Hz/Step
Voltmeter 4 digit, digital voltage meter, resolution 0.1V
Ammeter 4 digit, digital ammeter, resolution 0.1A
Watt meter 4 digit, digital Watt meter, resolution 0.1W
Protection With overload, short circuit, over temperature
Instantaneous power failure protection and alarm device
Working Environment Temperature 0 – 40 deg.℃
Humidity 0 – 90% (Non condensation)
Warranty 18 months